TeSys GV electrical trip, MN undervoltage release, 380-400V AC 50Hz / 440V AC 60Hz, for motor circuit breakers GV2ME used in safety-related systems. It trips the circuit breaker when the control voltage drops below 0.35 Uc, possible opening between 0.35-0.7 Uc. Closing of the circuit breaker is only possible when the control voltage is applied in the range 0.85-1.1 Uc. To be mounted on right-hand side of the circuit breaker, connection by screw clamp terminals. Multi standards certified (IEC, UL, CSA, CCC, EAC, INRS, VDE 0113), Green Premium compliant (RoHS/REACh).
Specifications:
Range:
Product or Component Type:
Device Short Name:
Complementary:
- Range Compatibility:
- [Uc] Control Circuit Voltage:
- 380...400 V AC 50 Hz
- 440 V AC 60 Hz
- Control Circuit Voltage Limits: 0.85...1.1 Un
- [Ui] Rated Insulation Voltage:
- 690 V AC (IEC 60947-1)
- 600 V AC (UL 60947-4-1)
- 600 V AC (CSA C22.2 No 60947-4-1)
- Threshold Tripping Voltage: 0.7...0.35 Un
- Inrush Power:
- Hold-in Power Consumption:
- Operating Time: 10...15 ms (IEC 60947-1)
- On-load Factor: 100%
- Connections - Terminals:
- Screw Clamp Terminals:
- 1 cable(s) 1…2.5 mm² solid
- 2 cable(s) 1…2.5 mm² solid
- 1 cable(s) 0.75…2.5 mm² flexible without cable end
- 2 cable(s) 0.75…2.5 mm² flexible without cable end
- 1 cable(s) 0.75…1.5 mm² flexible with cable end
- 2 cable(s) 0.75…1.5 mm² flexible with cable end
- Tightening Torque: < 1.4 N.m on screw clamp terminals
- Mechanical Durability: 30,000 cycles
- Quantity Per Set: Set of 10
- Height: 89 mm
- Width: 18 mm
- Depth: 66 mm
- Net Weight: 0.105 kg
- Colour: Dark Grey