This spec is not available in the specification table.
Operating Temperature Range
-5°C to 55°C
This spec is not available in the specification table.
Mounting Type
DIN Rail
This spec is not available in the specification table.
Breaking Capacity
630A
This spec is not available in the specification table.
Standards and Certifications
IEC 60529
This spec is not available in the specification table.
Trip Curve
AC
This spec is not available in the specification table.
Dimensions
(W) 36mm x (H) 81mm x (D) 68mm
This spec is not available in the specification table.
Rated Voltage
220VAC to 240VAC
This spec is not available in the specification table.
Poles
2P
This spec is not available in the specification table.
Rated Current
63A
This spec is not available in the specification table.
Product Description
SCHNEIDER ELECTRIC Acti 9 Id K - Residual Current Circuit Breaker - 2P - 63A - 100mA - Type Ac A9KR15263
This Acti9 ID K product is a biconnect residual current circuit breaker (RCCB). It is a 2P circuit breaker with 63A In rated current, 100mA earth leakage sensitivity and AC type protection class. This product protects against electrical shock by indirect contact and fire hazards. There is a test button used to check the residual current device is operating correctly. The connection is made downstream by biconnect comb busbar or upstream/downstream by tunnel terminals. The connection is made downstream by biconnect comb busbar or upstream/downstream by tunnel terminals. The (Im/IΔm) rated breaking and making short circuit capacity is 630A. The (Inc/IΔc) conditional rated short circuit current is 4.5kA. It has an electrical endurance going up to 4000 cycles and a mechanical endurance going up to 5000 cycles. The Ue operational voltage is 220VAC to 240VAC. The Ui rated insulation voltage is 440VAC. The Uimp rated impulse withstand voltage is 4kV. The frequency is 50Hz. It is DIN rail mountable. The width in 9mm pitches is 4. The product colour is white (RAL9003). The dimensions are (W) 36mm x (H) 81mm x (D) 68mm. The weight is 0.18kg. According to IEC 60529 standard, the degree of protection is IP20 and IP40 in enclosure. The operating temperature is from -5°C to 55°C. The storage temperature is from -25°C to 85°C.
Range:Acti9
Product name:Acti9 iID
Product or component type:Residual current circuit breaker (RCCB)