4-pole, front operated, base mounted, DIN-rail mountable switch-diconnector / non-fusible diconnect switch with front protected clamp terminals, handle and shaft are not included
Product Net Width:96.5 mm
Product Net Height:100 mm
Product Net Depth / Length:74 mm
Product Net Weight:0.49 kg
Unit of measurement : Pcs
Technical
Rated Operational Current AC-21A (Ie):(380 ... 415 V) 100 A
(500 V) 100 A
(690 V) 100 A
Rated Operational Current AC-22A (Ie):(380 ... 415 V) 100 A
(500 V) 100 A
(690 V) 100 A
Rated Operational Current AC-23A (Ie):(380 ... 415 V) 80 A
(500 V) 60 A
(690 V) 40 A
Rated Operational Power AC-23A (Pe):(220 ... 240 V) 22 kW
(400 ... 415 V) 37 kW
(500 V) 37 kW
(690 V) 37 kW
Conventional Free-air Thermal Current (Ith):Θ = 40 °C 115 A
Conventional Thermal Current (Ithe):Fully Enclosed 115 A
Rated Impulse Withstand Voltage (Uimp):8 kV
Rated Insulation Voltage (Ui):acc. to IEC/EN 60664-1 750 V
Rated Operational Voltage:Main Circuit 750 V
Rated Short-Circuit Making Capacity (Icm):(690 V) 3.6 kA
Rated Short-time Withstand Current Low Voltage (Icw):for 1 s 2.5 kA
Rated Conditional Short-Circuit Current (Inc):(125 A fuse, 415 V) 50 kA
(125 A fuse, 690 V) 10 kA
(63 A fuse, 690 V) 50 kA
Power Loss:at Rated Operating Conditions per Pole 4.0 W
Pollution Degree:3
Handle Type:Knob
Handle and shaft not included
Fourth Pole Position:Right Side
Fourth Pole Type:Switched - Simultaneous Function
Switches Operating Mechanism:Mechanism on Top of the Switch