Abb AX32-30-10-80 Contactor 3P 9KW 3NO 1AUX 50/60HZ 230-240VAC
Abb AX32-30-10-80 Contactor 3P 9KW 3NO 1AUX 50/60HZ 230-240VAC
Brand:
ABB
Model:
AX32-30-10-80
Image
Image
Product Description

Abb AX32-30-10-80 Contactor 3P 9KW 3NO 1AUX 50/60HZ 230-240VAC

  • Extended Product Type:AX32-30-10-80
  • Product ID:1SBL281074R8010
  • EAN:3471522399809
  • Catalog Description:AX32-30-10-80 220-230V50Hz/230-240V60Hz Contactor
  • Long Description:AX32, AX40 contactors are mainly used for controlling 3-phase motors and power circuits up to 690 V AC. These contactors are of the block type design with: – 3 main poles and 1 built-in auxiliary contact – control circuit: AC operated – add-on auxiliary contact blocks for front or side mounting and a wide range of accessories.
  • Number of Main Contacts NO:3
  • Number of Main Contacts NC:0
  • Number of Auxiliary Contacts NO:1
  • Number of Auxiliary Contacts NC:0
  • Rated Operational Voltage:Auxiliary Circuit 690 V
  • Main Circuit 690 V
  • Rated Frequency (f):Auxiliary Circuit 50 / 60 Hz
  • Main Circuit 50 / 60 Hz
  • Conventional Free-air Thermal Current (Ith):acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 65 A
  • acc. to IEC 60947-5-1, Θ = 40 °C 16 A
  • Rated Operational Current AC-1 (Ie):(220 / 240 V) 55 °C 55 A
  • (690 V) 40 °C 55 A
  • (690 V) 70 °C 39 A
  • Rated Operational Current AC-3 (Ie):(415 V) 55 °C 32 A
  • (440 V) 55 °C 32 A
  • (500 V) 55 °C 28 A
  • (690 V) 55 °C 21 A
  • (380 / 400 V) 55 °C 32 A
  • (220 / 230 / 240 V) 55 °C 32 A
  • Rated Operational Power AC-3 (Pe):(415 V) 15 kW
  • (440 V) 18.5 kW
  • (500 V) 18.5 kW
  • (690 V) 18.5 kW
  • (380 / 400 V) 15 kW
  • (220 / 230 / 240 V) 9 kW
  • Rated Operational Current AC-15 (Ie):(500 V) NC 2
  • (500 V) 2 A
  • (690 V) 2 A
  • (24 / 127 V) 6 A
  • (220 / 240 V) 4 A
  • (380 / 400 V) 3 A
  • (400 / 440 V) 2 A
  • Rated Short-time Withstand Current Low Voltage (Icw):at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 400 A
  • at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 65 A
  • at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 150 A
  • at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 600 A
  • at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 225 A
  • for 0.1 s 140 A
  • for 1 s 100 A
  • Maximum Breaking Capacity:cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 820 A
  • cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 340 A
  • Maximum Electrical Switching Frequency:(AC-1) 600 cycles per hour
  • (AC-15) 1200 cycles per hour
  • (AC-3) 1200 cycles per hour
  • (DC-13) 900 cycles per hour
  • Rated Operational Current DC-13 (Ie):(24 V) 6 A / 144 W
  • (110 V) 1.1 A / 121 W
  • (125 V) 1.1 A / 138 W
  • (220 V) 0.55 A / 121 W
  • (250 V) 0.55 A / 138 W
  • (400 V) 2.8 A / 134 W
  • (500 V) 2 A / 144 W
  • Rated Insulation Voltage (Ui):acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
  • Rated Impulse Withstand Voltage (Uimp):Auxiliary Circuit 6 kV
  • Maximum Mechanical Switching Frequency:3600 cycles per hour
  • Rated Control Circuit Voltage (Uc):50 Hz 220 ... 230 V
  • 60 Hz 230 ... 240 V
  • Operate Time:Between Coil De-energization and NC Contact Closing 7 ... 14 ms
  • Between Coil De-energization and NO Contact Opening 4 ... 11 ms
  • Between Coil Energization and NC Contact Opening 6 ... 18 ms
  • Between Coil Energization and NO Contact Closing 8 ... 21 ms
  • Degree of Protection:acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
  • acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
  • acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
  • IP20
  • Terminal Type:Screw Terminals
  • Unit of Measurement : Pcs
Highly Matched Items
View items that have the same or are a close match to the specifications of this item
Contactors from ABB
Source & compare similar products
More from Contactors
Expand your search with a wider selection
Recently Viewed Products
Compare & Refer to previously viewed items
Image
Top