Long Description:The AF116-30-11-13 is a 3 pole - 690 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and double clamp, controlling motors up to 55 kW / 400 V AC (AC-3) or 75 hp / 480 V UL and switching power circuits up to 160 A (AC-1) or 160 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Number of Main Contacts NO:3
Number of Main Contacts NC:0
Number of Auxiliary Contacts NO:1
Number of Auxiliary Contacts NC:1
Rated Operational Voltage:Main Circuit 690 V
Rated Frequency (f):Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith):acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 160 A
Rated Operational Current AC-1 (Ie):(690 V) 40 °C 160 A
(690 V) 60 °C 145 A
(690 V) 70 °C 130 A
Rated Operational Current AC-3 (Ie):(415 V) 55 °C 116 A
(440 V) 55 °C 116 A
(500 V) 55 °C 110 A
(690 V) 55 °C 65 A
(380 / 400 V) 55 °C 116 A
(220 / 230 / 240 V) 55 °C 116
Rated Operational Current AC-3e (Ie):(415 V) 60 °C 116 A
(440 V) 60 °C 116 A
(500 V) 60 °C 110 A
(690 V) 60 °C 65 A
(380 / 400 V) 60 °C 116 A
(220 / 230 / 240 V) 60 °C 116 A
Rated Operational Power AC-3 (Pe):(415 V) 55 kW
(440 V) 75 kW
(500 V) 75 kW
(690 V) 55 kW
(380 / 400 V) 55 kW
(220 / 230 / 240 V) 30 kW
Rated Operational Power AC-3e (Pe):(415 V) 55 kW
(440 V) 75 kW
(500 V) 75 kW
(690 V) 55 kW
(380 / 400 V) 55 kW
(220 / 230 / 240 V) 30 kW
Rated Breaking Capacity AC-3:8 x Ie AC-3
Rated Breaking Capacity AC-3e:8.5 x Ie AC-3e
Rated Making Capacity AC-3:10 x Ie AC-3
Rated Making Capacity AC-3e:12 x Ie AC-3e
Short-Circuit Protective Devices:gG Type Fuses 250 A
Rated Short-time Withstand Current Low Voltage (Icw):at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 928 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 160 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 379 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1160 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 536 A
Maximum Breaking Capacity:cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 2000 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 1000 A
Maximum Electrical Switching Frequency:(AC-1) 300 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 300 cycles per hour
Rated Operational Current DC-1 (Ie):(110 V) 2 Poles in Series, 40 °C 145 A
(220 V) 3 Poles in Series, 40 °C 145 A
Rated Operational Current DC-3 (Ie):(110 V) 2 Poles in Series, 40 °C 145 A
(220 V) 3 Poles in Series, 40 °C 145 A
Rated Operational Current DC-5 (Ie):(110 V) 2 Poles in Series, 40 °C 145 A
(220 V) 3 Poles in Series, 40 °C 145 A
Rated Insulation Voltage (Ui):acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp):Main Circuit 8 kV
Mechanical Durability:5 million
Maximum Mechanical Switching Frequency:300 cycles per hour
Coil Operating Limits:(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc):50 Hz 100 ... 250 V
60 Hz 100 ... 250 V
DC Operation 100 ... 250 V
Coil Consumption:Holding at Max. Rated Control Circuit Voltage 50 Hz 6 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 6 V·A
Holding at Max. Rated Control Circuit Voltage DC 3 W
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 130 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 130 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 135 W
Operate Time:Between Coil De-energization and NO Contact Opening 37 ... 47 ms
Between Coil Energization and NO Contact Closing 25 ... 55 ms
Connecting Capacity Main Circuit:Flexible 2 x 10 ... 70 mm²