Application
Operating temperature-20°C to +60°CCalibration temperature20...28°CRelative humidity< 95% RH (non-cond.)Protection degree (mounted in panel)IP65 / Type 4X
Dimensions (HxWxD)48 x 96 x 120 mmCut out dimensions44.5 x 91.5 mmWeight approx.230 gWire size, pin 41-46 (max.)0.05...1.31 mm2 AWG 30...16 stranded wireWire size, others, max.0.05...3.31 mm2 / AWG 30...12 stranded wireVibrationIEC 60068-2-62...13.2 Hz±1 mm13.2...100 Hz±0.7 g
Supply voltage, universal21.6...253 VAC, 50...60 Hz or 19.2...300 VDCMax. required power2.5 W (5714A) 3.0 W (5714B/C)
3.5 W (5714D)
Internal power dissipation2.2 W (5714A) 2.7 W (5714B/C)
3.2 W (5714D)
Isolation voltage, test / working2.3 kVAC / 250 VAC
Temperature input, programmable (0...90%, 100...10%)1...60 smA / V input (programmable)0.4...60 s
2-wire supply (pin 46...45)> 15 VDC @ 0...20 mASignal / noise ratioMin. 60 dB (0...100 kHz)AccuracyBetter than 0.1% of sel. rangeEMC immunity influence< ±0.5% of readout
RTD typePt10/20/50/100/200/250; Pt300/400/500/1000; Ni50/100/120/1000; Cu10/20/50/100Cable resistance per wire50 Ω (max.)Sensor currentNom. 0.2 mAEffect of sensor cable resistance (3-/4-wire)< 0.002 Ω / Ω
Linear resistance min....max.0 Ω...10000 Ω
Potentiometer min....max.10 Ω...100 kΩ
Thermocouple typeB, E, J, K, L, N, R, S, T, U, W3, W5, LRCJC via int. mounted sensor±(2.0°C + 0.4°C * Δt)Sensor error detectionYesSensor error current: When detecting / elseNom. 2 μA / 0 μA
Measurement range0...23 mAProgrammable measurement ranges0...20 and 4...20 mAInput resistanceNom. 20 Ω + PTC 25 ΩSensor error detectionLoop break 4...20 mA
Measurement range0...12 VDCProgrammable measurement ranges0/0.2...1; 0/2...10 VDCInput resistanceNom. 10 MΩ
Display readout-1999...9999 (4 digits)Decimal pointProgrammableDigit height13.8 mmDisplay updating.2.2 times / sInput outside input range is indicated byExplanatory text
Signal range0...23 mAProgrammable signal ranges0...20/4...20/20...0/20...4 mALoad (@ current output)≤ 800 ΩLoad stability≤ 0.01% of span / 100 ΩSensor error indication0 / 3.5 / 23 mA / noneNAMUR NE43 Upscale/Downscale23 mA / 3.5 mAOutput limitation, on 4...20 and 20...4 mA signals3.8...20.5 mAOutput limitation, on 0...20 and 20...0 mA signals0...20.5 mACurrent limit≤ 28 mA
Relay functionsSetpointHysteresis0...100%ON and OFF delay0...3600 sSensor error reactionBreak / Make / HoldMax. voltage250 VAC / VDCMax. current2 AMax. AC power500 VAMax. DC current, resistive load > 30 VDCSee manual for details
EMC2014/30/EU & UK SI 2016/1091LVD2014/35/EU & UK SI 2016/1101RoHS2011/65/EU & UK SI 2012/3032EACTR-CU 020/2011EAC LVDTR-CU 004/2011
c UL us, UL 508E248256EU RO MR Type ApprovalMRA000000Z