Shopping List
Shopping List
MYR - RM
Image
/
/
/
/
Schneider Electric Acti 9 K60N 1P - 16 a - B Curve 6000 A
Schneider Electric Acti 9 K60N 1P - 16 a - B Curve 6000 A
Image
Image
Technical Data Sheets
Product Description

SCHNEIDER ELECTRIC Acti 9 K60N 1P - 16 a - B Curve 6000 A

Main

  • Device application Distribution
  • Range Acti9
  • Product name Acti9 K60
  • Product or component type
  • Miniature circuit-breaker
  • Device short name K60N
  • Poles description 1P
  • Number of protected poles 1
  • [In] rated current 16 A
  • Network type AC
  • Trip unit technology Thermal-magnetic
  • Curve code B
  • Breaking capacity 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/
  • IEC 60898-1
  • Utilisation category Category A conforming to IEC 60947-2
  • Suitability for isolation Yes conforming to EN/IEC 60898-1
  • Standards EN/IEC 60898-1
  • Product certifications VDE
  • OVE

Complementary

  • Network frequency 50/60 Hz
  • Magnetic tripping limit 3...5 x In
  • [Ics] rated service breaking capacity 6000 A 100 % conforming to EN/IEC 60898-1 - 230 V AC 50/60 Hz
  • Limitation class 3 conforming to EN/IEC 60898-1
  • [Ui] rated insulation voltage 440 V AC 50/60 Hz conforming to EN/IEC 60898-1
  • [Uimp] rated impulse withstand voltage 4 kV conforming to EN/IEC 60898-1
  • Contact position indicator No
  • Control type Toggle
  • Local signalling Without
  • Mounting mode Fixed
  • Mounting support DIN rail
  • Comb busbar and distribution block compatibility Downside: biconnect 9 mm pitches 2
  • Height 81 mm
  • Width 18 mm
  • Depth 70 mm
  • Net weight 0.12 kg
  • Colour White
  • Mechanical durability 20000 cycles
  • Electrical durability 20000 cycles
  • Connections - terminals Tunnel type terminals (downstream) 0.5…35 mm² rigid
  • Tunnel type terminals (upstream) 0.5…35 mm² rigid
  • Tunnel type terminals (downstream) 0.5…25 mm² flexible
  • Tunnel type terminals (upstream) 0.5…25 mm² flexible
  • Wire stripping length 14 mm for top or bottom connection
  • Tightening torque 3.5 N.m top or bottom
  • Earth-leakage protection Without 2

Environment

  • IP degree of protection IP20 conforming to IEC 60529
  • Pollution degree 2 conforming to IEC 60898-1
  • 2 conforming to EN 60898-1
  • Overvoltage category II
  • Tropicalisation 2 conforming to IEC 60068-1
  • Relative humidity 95 % at 55 °C
  • Operating altitude 0...2000 m
  • Ambient air temperature for operation -25…70 °C
  • Ambient air temperature for storage -25…85 °C

Packing Units

  • Unit Type of Package 1 PCE
  • Number of Units in Package 1 1
  • Package 1 Height 1.7 cm
  • Package 1 Width 7.5 cm
  • Package 1 Length 8.5 cm
  • Package 1 Weight 106 g
  • Unit Type of Package 2 BB1
  • Number of Units in Package 2 12
  • Package 2 Height 8 cm
  • Package 2 Width 9 cm
  • Package 2 Length 23 cm
  • Package 2 Weight 1.338 kg
  • Unit Type of Package 3 S03
  • Number of Units in Package 3 144
  • Package 3 Height 30 cm
  • Package 3 Width 30 cm
  • Package 3 Length 40 cm
  • Package 3 Weight 16.744 kg
Highly Matched Items
View items that have the same or are a close match to the specifications of this item
Circuit Breaker from SCHNEIDER ELECTRIC
Source & compare similar products
More from Circuit Breaker
Expand your search with a wider selection
Recently Viewed Products
Compare & Refer to previously viewed items
Image
Top