Schneider Electric TMCR2TI2 2 Temperature Inputs - Cartridge M200
Specifications:
- Range of Product: Easy Modicon M200
- Product or Component Type: Analogue input cartridge
- Product Compatibility: Easy Modicon M200
- Analogue Input Number: 2
- Complementary:
- Analogue Input Type:
- Thermocouple:
- -200 to 1000 °C with thermocouple J
- -200 to 1300 °C with thermocouple K
- 0 to 1760 °C with thermocouple R
- 0 to 1760 °C with thermocouple S
- 0 to 1820 °C with thermocouple B
- -200 to 400 °C with thermocouple T
- -200 to 1300 °C with thermocouple N
- -200 to 800 °C with thermocouple E
- 0 to 2315 °C with thermocouple C
- Ni 100/Ni 1000 temperature probe: 60 to 180 °C
- Pt 100 temperature probe: 200 to 850 °C
- Pt 1000 temperature probe: 200 to 600 °C
- Analogue Input Resolution: 14 bits
- LSB Value: 0.1 °C
- Sampling Duration:
- 125 ms for thermocouples
- 250 ms for temperature probes
- Absolute Accuracy Error: Varied based on input type and temperature range
- Temperature Drift: ±0.02 %FS/°C
- Repeat Accuracy: ±0.5 %FS
- Non-Linearity: ±0.01 %FS
- Cross Talk: ≤ 1 LSB
- Type of Cable: Twisted shielded pairs cable
- Electrical Connection: 3 x 1.5 mm² 2 screw terminal blocks with pitch 3.81 mm adjustment for inputs
- Maximum Cable Distance Between Devices: <30 m for input using twisted shielded pairs cable
- Insulation: Non-insulated between analogue input and internal logic
- Dimensions:
- Height: 41 mm
- Depth: 15 mm
- Width: 35 mm
- Net Weight: 0.012 kg
- Input Impedance: ≥ 1 MOhm
- Environment:
- Immunity to Microbreaks: 10 ms