This product is part of the Modicon M171/M172 range, an offer I/O modules for HVAC solutions. This additional I/O module offers 8 discrete inputs with sink or source (positive/negative) discrete input logic. It is a module with discrete input voltage ranges from 24V AC/DC to 48V DC and analogue output voltage ranges from 0V to 15V. This module offers 3 SPST relay output, 2 SPST relay output with same common and 2 SPDT relay output with independent common discrete output. It is an IP20 rated product. Its dimensions are 140mm (width) x 61.6mm (depth) x 110mm (height). It weighs 0.19kg. The main application of this module is HVAC and pumping solution. Modicon M171/M172 benefits maximize profitability and energy efficiency by using scalable automation control with the Modicon M171/M172. Modicon M171/M172 logic controllers and intuitive software EcoStruxure Machine Expert - HVAC are designed for maximizing profitability and energy efficiency.
Specifications:
- Range of Product: Modicon M171/M172
- Product or Component Type: Additional I/O Module
- Product Specific Application: HVAC and pumping solution
- Total Inputs/Outputs: 27
- Discrete Input Number: 8
- Discrete Output Number:
- 3 for relay outputs SPST with the same common
- 2 for relay outputs SPST with the same common
- 2 for relay outputs SPDT with independent common
- Discrete Output Current:
- 8 A for relay SPDT
- 5 A for relay SPST
- Analog Input Number:
- 2 analog input NTC
- 4 configurable
- Analog Output Number:
- 3 voltage/current, range: 0-10 V or 4-20 mA
- 2 open collector/current, range: 1 kHz, 12 V, 35 mA or 4-20 mA
- Complementary:
- Number of Port: 1 CAN port - screw terminal block
- Input/Output Number:
- 6 analog inputs
- 5 analog outputs
- 8 digital inputs
- 7 digital outputs
- 1 high-speed counter
- Discrete Input Logic: Sink or source (positive/negative)
- Discrete Input Voltage: 24 V AC/DC, 48 V DC
- Discrete Input Current: 2.5 mA
- Input Impedance: 20 kOhm
- Analog Input Type: Various types including voltage, current, impedance, temperature probes, and direct input
- Sensor Power Supply:
- 5 V DC at 50 mA
- 12 V DC at 150 mA
- [Us] Rated Supply Voltage: 24 V AC, 48 V
- Real-Time Clock: Without clock at -20-55 °C
- Display Type: Without display
- Overvoltage Category: II
- Mounting Support: DIN rail
- Width: 140 mm
- Height: 110 mm
- Depth: 61.6 mm
- Net Weight: 0.19 kg
- Environment:
- Directives: 86/188/EEC - physical agents (noise) directive, 2006/95/EC - low voltage directive
- Standards: EN/IEC 60730
- Ambient Air Temperature:
- For Operation: -20-55 °C conforming to UL 60730-1
- For Storage: -40-85 °C
- Relative Humidity: 10-90%, non-condensing
- IP Degree of Protection: IP20
- Pollution Degree: 2