Shopping List
Shopping List
AUD - AU$
Image
/
/
/
/
Schneider Electric LV429671 Tmd - Circuit Breaker Compact NSX100H
Schneider Electric LV429671 Tmd - Circuit Breaker Compact NSX100H
Image
Image
Specifications
infotip-icon
View other Molded Case Circuit Breakers - MCCBs dimensions or variations
Please select at least one specification below.
Poles
3
Rated Current
80A
Operating Temperature Range
"-25-70 °C"
This spec is not available in the specification table.
Rated Voltage
690 V AC 50/60 Hz
This spec is not available in the specification table.
Dimensions
105 mm x 161 mm x 86 mm
This spec is not available in the specification table.
Weight
2.05 kg
This spec is not available in the specification table.
Breaking Capacity
"10 kA at 600 V AC 50/60 Hz conforming to UL 508, 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2, 100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2, 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2, 65 kA at 480 V AC 50/60 Hz conforming to UL 508, 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2, 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 85 kA at 240 V AC 50/60 Hz conforming to UL 508"
This spec is not available in the specification table.
Standards and Certifications
EN/IEC 60947, CCC, EAC, Marine
This spec is not available in the specification table.
Trip Curve
TMD
This spec is not available in the specification table.
Mounting Type
Backplate
This spec is not available in the specification table.
Product Description

SCHNEIDER ELECTRIC Circuit Breaker Compact NSX100H - Tmd - 80 a - 3 Poles 3d LV429671

MAIN SPECIFICATIONS

  • Breaking Capacity 10 kA at 600 V AC 50/60 Hz conforming to UL 508
  • 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
  • 100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
  • 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
  • 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
  • 65 kA at 480 V AC 50/60 Hz conforming to UL 508
  • 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
  • 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
  • 85 kA at 240 V AC 50/60 Hz conforming to UL 508
  • Breaking Capacity Code H 70 kA 415 V AC
  • Contacts Type And Composition 80 A at 40 °C
  • Control Type toggle
  • Product Or Component Type circuit breaker
  • Range Of Product ComPact NSX100...250
  • Trip Unit Name TM-D
  • [Ie] Rated Operational Current toggle
  • [Ue] Rated Operational Voltage 690 V AC 50/60 Hz
  • Device Short Name NSX100H
  • EAN13 3606480009020
  • Mounting Support backplate
  • Network Type AC
  • Protected Poles Description 3t
  • Range ComPact
  • Range Name ComPact NSX
  • Suitability For Isolation yes conforming to EN/IEC 60947-2
  • Trip Unit Protection Functions LI
  • Trip Unit Technology thermal-magnetic
  • Utilisation Category category A

COMPLEMENTARY

  • Communication Network Type 690 V AC 50/60 Hz
  • Current Transformer Type H 70 kA 415 V AC
  • Interlocked Device 10 kA at 600 V AC 50/60 Hz conforming to UL 508
  • 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
  • 100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
  • 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
  • 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
  • 65 kA at 480 V AC 50/60 Hz conforming to UL 508
  • 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
  • 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
  • 85 kA at 240 V AC 50/60 Hz conforming to UL 508
  • Product Name ComPact NSX
  • [Ics] Rated Service Breaking Capacity 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
  • 100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
  • 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
  • 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
  • 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
  • 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
  • [In] Rated Current 80 A at 40 °C
  • Compatibility Code NSX100
  • Connection Pitch 35 mm
  • Depth 86 mm
  • Device Application distribution
  • Downside Connection front
  • Earth-leakage Protection without
  • Electrical Durability 10000 cycles at 690 V In
  • 20000 cycles at 690 V In/2
  • 30000 cycles at 440 V In
  • 50000 cycles at 440 V In/2
  • Height 161 mm
  • Long Time Delay Adjustment Type fixed
  • Long Time Pick-up Adjustment Range 0.7...1 x In
  • Long Time Pick-up Adjustment Type Ir adjustable
  • Mechanical Durability 50000 cycles
  • Mounting Mode fixed
  • Net Weight 2.05 kg
  • Network Frequency 50/60 Hz
  • Number Of Slots 5 slot(s)
  • Protection Type I : for short-circuit protection (magnetic)
  • L : for overload protection (thermal)
  • Short-time Delay Adjustment Type fixed
  • Short-time Pick-up Adjustment Type Isd fixed
  • Trip Unit Rating 80-80 A at 40 °C
  • Upside Connection front
  • Width 105 mm
  • [Isd] Short-time Pick-up Adjustment Range 640 A
  • [tr] Long-time Delay Adjustment Range 120-400 s at 1.5 x In
  • 15-15 s at 6 x Ir
  • [Uimp] Rated Impulse Withstand Voltage 8 kV
  • [Ui] Rated Insulation Voltage 800 V AC 50/60 Hz

ENVIRONMENT

  • Ambient Air Temperature For Operation -25-70 °C
  • Ambient Air Temperature For Storage -50-85 °C
  • Electrical Shock Protection Class class II
  • IK Degree Of Protection IK07 conforming to IEC 62262
  • IP Degree Of Protection IP40 conforming to IEC 60529
  • Operating Altitude 0...2000 m without derating
  • 2000 m...5000 m with derating
  • Overvoltage Category class II
  • Pollution Degree 3 conforming to IEC 60664-1
  • Product Certifications CCC
  • EAC
  • Marine
  • Relative Humidity 0-95 %
  • Standards EN/IEC 60947

OTHER

  • Earth Leakage Current TM-D
  • Poles Description 3P
  • [Us] Rated Supply Voltage ComPact NSX100...250


AU $ 468.37
Image
Lead time of 60 working days required.
Item will be ready to dispatch within the lead time specified.
Quantity:
EA
Highly Matched Items
View items that have the same or are a close match to the specifications of this item
Molded Case Circuit Breakers - MCCBs from SCHNEIDER ELECTRIC
Source & compare similar products
More from Molded Case Circuit Breakers - MCCBs
Expand your search with a wider selection
Recently Viewed Products
Compare & Refer to previously viewed items
Image