TeSys LT3 thermistor protection unit for use with PTC probes, with automatic reset and fault indicator on front, dual voltage supply 115 or 230V AC 50/60Hz. To be used with a combination of PTC probes impedance lower than 1500 Ohm at 25°C, the trip impedance zone is 2700-3100 Ohm, the automatic reset impedance zone is 1500-1650 Ohm. It provides 2 auxiliary contacts 1NO+1NC for fault signaling. DIN rail mounting, connections by cage terminals. PTC thermistor probes DA1TT, DA1TS available (to be ordered separately). Multi-standards certified (IEC, UL, CSA), Green Premium compliant (RoHs/Reach).
Main
- Range of Product: LT3
- Device Short Name: LT3SA
- Product or Component Type: Thermistor Protection Units
- [Uc] Control Circuit Voltage: 115/230 V AC 50/60 Hz
- Reset: Automatic Reset
Complementary
- Control Circuit Voltage Limits: 0.85...1.1 Uc
- Contacts Type and Composition: 1 NC + 1 NO Dual Voltage
- [Ith] Conventional Free Air Thermal Current: 5 A for Output Control Relay
- [Ui] Rated Insulation Voltage: Output Control Relay: 500 V AC
- [Ue] Rated Operational Voltage: 250 V AC 50/60 Hz for Output Control Relay
- Signalling Function:
- Fault Indication
- Voltage Indication
- Control Type: Automatic Reset
- Probe Interchangeability: Label Mark A conforming to IEC 60034-11
- Hold-in Power Consumption:
- Resistance:
- Reset: 1500…1650 Ohm
- Tripping: 2700…3100 Ohm
- Number of Probes: 0…6
- Input Voltage:
- < 2.5 V (1500 Ohm) for Probe
- < 7.5 V (4000 Ohm) for Probe conforming to IEC 60034-11
- Maximum Short Circuit Detection Resistance: 20 Ohm
- Condition of Use:
- Connection of Probes 400 m >1 mm²
- Connection of Probes 500 m >1.5 mm²
- [Uimp] Rated Impulse Withstand Voltage: 2.5 kV
- Rated Power in VA: 100 VA at 220 V - Electrical Durability: 500,000 cycles
- Breaking Capacity:
- 2 A at 24 V DC DC-13
- 3 A at 250 V AC AC-16
- 6 A at 120 V AC AC-16
- Connections - Terminals:
- Power circuit: cage type connector 1 cable(s) 0.75…2.5 mm²flexible with cable end
- Power circuit: cage type connector 1 cable(s) 0.75…2.5 mm²solid with cable end
- Power circuit: cage type connector 1 cable(s) 1…2.5 mm²flexible without cable end
- Power circuit: cage type connector 1 cable(s) 1…2.5 mm²solid without cable end
- Power circuit: cage type connector 2 cable(s) 0.75…2.5 mm²flexible with cable end
- Power circuit: cage type connector 2 cable(s) 0.75…2.5 mm²solid with cable end
- Power circuit: cage type connector 2 cable(s) 1…2.5 mm²flexible without cable end
- Power circuit: cage type connector 2 cable(s) 1…2.5 mm²solid without cable end
- Tightening Torque: 0.8 N.m
- Height: 100 mm
- Width: 22.5 mm
- Depth: 100 mm
- Net Weight: 0.22 kg
Environment
- Standards:
- IEC 60947-8
- IEC 60034-11
- VDE 0660
- IP Degree of Protection: IP20 conforming to IEC 60529, IP20 conforming to VDE 0106
- Ambient air temperature for operation: -25…60 °C
- Ambient air temperature for storage:
- -40…85 °C conforming to IEC 60068-2-2
- -40…85 °C conforming to IEC 60068-2-2
- Operating Altitude:
- <= 1500 m without derating in temperature
- > 1500...3000 m with derating in temperature
- Vibration Resistance:
- 1 gn 25...150 Hz conforming to IEC 60068-2-6
- 2.5 gn 2...25 Hz conforming to IEC 60068-2-6
- Shock Resistance: 5 gn 11 ms conforming to IEC 60068-2-27
- Electromagnetic Compatibility:
- Resistance to Electrostatic Discharge Level 3 conforming to IEC 61000-4-2
- Resistance to Fast Transient Level 3 conforming to IEC 61000-4-4
- Surge Resistance 1.2/50-8/20 Level 4 conforming to IEC 61000-4-5
- Susceptibility to Electromagnetic Fields Level 3 conforming to IEC 61000-4-3
- Immunity to Microbreaks and Voltage Drops conforming to IEC 61000-4-11