TeSys Deca time delay auxiliary contact block, for contactors LC1D, LC1F and control relays CAD. It provides 1NO+1NC contacts rated up to 10A 690V AC, Off-delay setting range 10-180s, connection by screw clamp terminals. Clip-on front mounting, it procures high reliability and durability. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHs/Reach).
Main
- Range: TeSys, TeSys Deca
- Product Name: TeSys Deca
- Product or Component Type: Time Delay Auxiliary Contact Block
- Range Compatibility:
- TeSys Deca CAD
- TeSys Deca LC1D
- TeSys F LC1F
- TeSys F CR1F
- Mounting Location: Front
- Pole Contact Composition: 1 NO + 1 NC
- Contacts Operation: Time Delay
- Timer Type: Off Delay
- Time Delay Range: 10...180 s
- [Ue] Rated Operational Voltage: 690 V AC 25...400 Hz
- [Ie] Rated Operational Current:
- 6 A at 120 V AC-15
- 1.04 A at 690 V AC-15
- 0.55 A at 125 V DC-13
- 0.1 A at 600 V DC-13
- [Ui] Rated Insulation Voltage:
- 690 V conforming to IEC 60947-5-1
- 600 V conforming to UL 60947-5-1
- 600 V conforming to CSA C22.2 No 60947-5-1
- [Ith] Conventional Free Air Thermal Current: 10 A (at 60 °C)
- Standards: GB/T 14048.5
- Product Certifications:
- IECEE CB Scheme
- UL
- CSA
- CCC
- EAC
- UKCA
Complementary:
- Irms Rated Making Capacity:
- 140 A at <= 690 V AC conforming to IEC 60947-5-1
- 250 A at <= 690 V DC conforming to IEC 60947-5-1
- Permissible Short-time Rating:
- 100 A 60 °C 1 s
- 120 A 60 °C 500 ms
- 140 A 60 °C 100 ms
- Protection Type: GG fuse 10 A
- Mechanical Durability: 5 Mcycles
- Minimum Switching Current: 5 mA
- Minimum Switching Voltage: 17 V
- Non-overlap Time:
- 1.5 ms on de-energisation no overlap between NC and NO contact
- 1.5 ms on energisation no overlap between NC and NO contact
- Insulation Resistance: > 10 MOhm
- Connections - Terminals:
- Screw clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end
- Screw clamp terminals 1 cable(s) 1…2.5 mm²flexible without cable end
- Screw clamp terminals 1 cable(s) 1…2.5 mm²rigid
- Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
- Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible without cable end
- Screw clamp terminals 2 cable(s) 1…2.5 mm²rigid
- Screw clamp terminals
- Tightening Torque:
- 1.7 N.m - with screwdriver flat Ø 6 mm
- 1.7 N.m - with screwdriver Philips No 2
- 1.7 N.m - with screwdriver pozidriv No 2
- Dimensions:
- Height: 48 mm
- Width: 44 mm
- Depth: 61 mm
- Colour: Dark grey
Environment
- Environmental Characteristic: Normal environment
- IP Degree of Protection: IP20 conforming to IEC 60529
- Protective Treatment: TH conforming to IEC 60068
- Ambient Air Temperature:
- Storage: -60…80 °C
- Operation: -40…70 °C
- Operating Altitude: 3000 m