TeSys Deca low signal interface module, for control of contactors LC.D09-D115 (3P). Electromechanical relay interface controlled by a 24V DC input signal. To be used with contactors with 24-250V AC coils (B7 to U7). To be mounted on a coil wiring adapter LAD4BB for contactors LC.D09-D38, LAD4BB3 for contactors LC.D40A-D80A, and directly on contactors LC.D80-D115. Green Premium compliant (RoHS/REACh).
Main
- Range: TeSys
- Device Short Name: LA4D
- Poles Description: 3P (3 Poles)
- Product or Component Type: Interface Module
- Product Compatibility: LC1D09 to LC1D150
Complimentary
- Mounting Mode: Top mounted
- Technology Type: Electromechanical
- Rated Supply Voltage ([Us]): 24 V DC
- Control Circuit Voltage Limits: 17 V to 30 V DC at 20°C
- Rated Insulation Voltage ([Ui]): 250 V (for control circuit conforming to IEC 60947-5-1)
- Connections - Terminals:
- Control circuit:
- Connector 1:
- Cable(s): 1 to 2.5 mm² flexible with cable end
- Cable(s): 1 to 2.5 mm² flexible without cable end
- Cable(s): 1 to 2.5 mm² solid with cable end
- Cable(s): 1 to 2.5 mm² solid without cable end
- Connector 2:
- Cable(s): 1 to 2.5 mm² flexible with cable end
- Cable(s): 1 to 2.5 mm² flexible without cable end
- Cable(s): 1 to 2.5 mm² solid with cable end
- Cable(s): 1 to 2.5 mm² solid without cable end
- Rated Operational Voltage ([Ue]): Control circuit: 24 V to 250 V AC
- Current Consumption: 25 mA at 20°C
- Current State 0 Guaranteed: ≤ 2 mA
- Voltage State 0 Guaranteed: < 2.4 V
- Voltage State 1 Guaranteed: 17 V
- Electrical Durability: 10 Mcycles at 240 V
- Local Signalling: LED indicator
- Height: 12 mm
- Net Weight: 0.05 kg
Environment
- Standards: IEC 60255-5
- Product Certifications: UL, CSA
- Conventional Free Air Thermal Current ([Ith]): 8 A at 50°C
- Protection Type: Built-in by diode
- IP Degree of Protection: IP2X conforming to IEC 60529
- Ambient Air Temperature for Operation: -25°C to 55°C
- Permissible Ambient Air Temperature around the Device: -25°C to 70°C
- Ambient Air Temperature for Storage: -40°C to 80°C
- Heat Dissipation: 0.6 W for control circuit
- Immunity to Microbreaks: 4 ms