50 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
4 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
This spec is not available in the specification table.
Width
45 mm
This spec is not available in the specification table.
Device Short Name
GV2ME
This spec is not available in the specification table.
Product Name
TeSys GV2
TeSys Deca
This spec is not available in the specification table.
Depth
78.5 mm
This spec is not available in the specification table.
Device Application
Motor protection
This spec is not available in the specification table.
Network Type
AC
This spec is not available in the specification table.
Connection Pitch
13.5 mm without spreader
This spec is not available in the specification table.
Network Frequency
50/60 Hz conforming to IEC 60947-4-1
This spec is not available in the specification table.
Utilisation Category
Category A conforming to IEC 60947-2
AC-3 conforming to IEC 60947-4-1
AC-3e conforming to IEC 60947-4-1
This spec is not available in the specification table.
Suitability for Isolation
Yes conforming to IEC 60947-1 § 7-1-6
This spec is not available in the specification table.
Standards
EN/IEC 60947-2
EN/IEC 60947-4-1
This spec is not available in the specification table.
Height
89 mm
This spec is not available in the specification table.
Mechanical Durability
100000 cycles
This spec is not available in the specification table.
Electrical Durability
100000 cycles for AC-3 at 415 V In
100000 cycles for AC-3e at 415 V In
This spec is not available in the specification table.
Fixing Mode
35 mm symmetrical DIN rail: clipped
Panel: screwed (with adaptor plate)
This spec is not available in the specification table.
Motor Power kW
9 kW at 400/415 V AC 50/60 Hz
11 kW at 500 V AC 50/60 Hz
18.5 kW at 690 V AC 50/60 Hz
This spec is not available in the specification table.
[Ith] conventional free air thermal current
23 A conforming to IEC 60947-4-1
This spec is not available in the specification table.
Power dissipation per pole
2.5 W
This spec is not available in the specification table.
Product certifications
CCC
UL
CSA
EAC
ATEX
LROS (Lloyds register of shipping)
BV
RINA
DNV-GL
UKCA
This spec is not available in the specification table.
Climatic withstand
conforming to IACS E10
This spec is not available in the specification table.
Fire resistance
960 °C conforming to IEC 60695-2-11
This spec is not available in the specification table.
Mechanical robustness
Shocks: 30 Gn for 11 ms
Vibrations: 5 Gn, 5...150 Hz
This spec is not available in the specification table.
[Ics] rated service short-circuit breaking capacity
100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
40 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
This spec is not available in the specification table.
Thermal protection adjustment range
17…23 A conforming to IEC 60947-4-1
This spec is not available in the specification table.
Magnetic tripping current
327 A
This spec is not available in the specification table.
Phase failure sensitivity
Yes conforming to IEC 60947-4-1
This spec is not available in the specification table.
Rated duty
Continuous conforming to IEC 60947-4-1
This spec is not available in the specification table.
IK Degree of Protection
IK04
This spec is not available in the specification table.