The IEC 309 HP system comprises plugs and socket-outlets from 16 to 125 A in two different versions – straight mobile and 10° flush-mounting – which have IP44/IP54 and IP66/IP67/IP68/IP69 degrees of protection (IP68/IP69 only available for straight versions). The introduction of all the hours references for the earthing contact completes the range for specific applications and installations. The 16-32 A versions are available with screw wiring or fast wiring with spring terminals, while the 63-125A versions propose indirect wiring with mantle terminals.
Spesifications
- Colour : Red
- Rated current (A) : 32
- IP degree : IP66/IP67
- No. of poles : 3P+N+E
- Mechanical resistance : IK09
- Reference h : 6
- Type : 10° angled flush-mounting socket outlet
- Rated voltage : 380-415 V
- Frequency : 50/60 Hz
- Terminal tightening capacity : 1-2.5mm² flexible cables - 1.5-4mm² rigid cables
- Operating temperature: -25 +55 °C
- Type of wiring : With screw
- Type of material : Halogen-free in compliance with EN 60754-2
- Electrocod : 2210
- Glow wire test: 850 °C (active parts) - 650 °C (passive parts)
- Total number of operations : > 2000
- Thermo-pressure with ball: 125 °C (active parts) - 80 °C (passive parts)
- Permissible overload : 42 A
- Breaking capacity at 1.1 UN : 40 A
- Insulation resistance : > 10 MΩ
- Ware number : 85366990
- Weight: 0.2kg